Cordex 3.6kW Modular Switched Mode Rectifier
Available in 75A @ 48Vdc
High power density, over 21kW per 23" shelf
Power limiting and wide range AC input
High efficiency and power factor correction Hot swappable, 4RU ultra compact design
Cordex rectifiers bring advanced technology to the DC power industry. Innovative engineering combines the best in efficiency and reliability meeting the power requirements for a variety of system applications. The fan cooled Cordex 3.6kW rectifier has extremely high density providing the most power in the least amount of space. A compact 4RU shelf accommodates six rectifiers per 23" shelf and five rectifiers per 19" shelf. Local and remote setup, adjustment, and control is a simple single-step process with the Cordex CXC System Controller. By utilizing TCP/IP technology, complete configuration and monitoring of power equipment is possible through a network web browser. brochure all rectifiers Cordex 3.6kW
Electrical Specifications
Input voltage |
| Nominal |
208 to 277Vac |
| Operating |
176 to 312Vac |
| Extended |
176 to 90Vac (derated power) |
| Input frequency |
45 to 66Hz |
| Power |
3600W continuous/module |
| Power factor |
>0.99 (50 to 100% load) |
| THD |
<5% |
| Efficiency |
>92% |
| Output voltage |
42 to 60Vdc |
| Float Voltage |
48 to 58Vdc |
| Output current |
66A @ 54Vdc (75A max. 48V) |
| Load regulation |
<±0.5% (static) |
| Line regulation |
<±0.1% (static) |
| Transient response |
±2% for 50 to 100% load step, 2ms recovery time |
Noise
| Voice band |
<32dBrnC |
| Wide band |
<30mV RMS (10kHz to 10MHz) |
|
<150mV pk to pk (10kHz to 100MHz) |
| Psophometric |
<1mV |
| Acoustic |
<60dBa @ 1m (3ft) |
Mechanical Specifications
| Dimensions (in/mm) |
6.3 x 3.4 x 11.8 / 160 x 87 x 300 |
| Weight (lb/kg) |
10 / 4.6 |
Features
| Indicators |
AC mains OK — green LED |
|
Module OK — green LED |
|
Module fail — red LED |
| Controls |
CAN interface to CXC Controller |
| Adjustments (via CXC Controller) |
Float voltage, Equalize voltage, High/Low voltage alarm, High voltage shutdown, Current limit, Slope, Start delay |
| Protection |
Current limit/short circuit, Start delay, Input/output fuses, Output high voltage shutdown, Power limiting, Thermal foldback/shutdown, Input transient, AC low line foldback/shutdown |
Environmental Specifications
| Operating Temperature |
-40 to 65°C / -40 to 149°F |
| Storage Temperature |
-40 to 85°C / -40 to 185°F |
| Humidity |
0 to 95% non-condensing |
| Elevation |
-500 to 4000m / -1640 to 13120ft |
| Heat dissipation |
<1176BTU per hour |
Standards
| Safety |
CSA C22.2 No 60950-1-03 |
|
UL 60950-1 1st Edition |
|
CE marked |
|
IEC/EN 60950-1 |
| EMC |
ETSI 300 386 |
| Emissions |
CFR47 (FCC) Part 15 Class B |
|
ICES-03 Class B |
|
EN55022 (CISPR 22) Class B |
|
C-tick (Australia) |
|
EN 61000-3-2 |
|
EN 61000-3-3 |
| Immunity |
EN 61000-4-2 |
|
EN 61000-4-3 |
|
EN 61000-4-4 |
|
EN 61000-4-5 |
|
EN 61000-4-6 |
|
EN 61000-4-11 |
|
ANSI/IEEE C62.41 Cat B3 |
| NEBS |
GR-1089 CORE |
|
GR-69 CORE |
|