Cordex 3.6kW Modular Switched Mode Rectifier
- Available in 75A @ 48Vdc
- High power density, over 21kW per 23" shelf
- Power limiting and wide range AC input
- High efficiency and power factor correction
- Hot swappable, 4RU ultra compact design
Cordex rectifiers bring advanced technology to the DC power industry. Innovative engineering combines the best in efficiency and reliability meeting the power requirements for a variety of system applications. The fan cooled Cordex 3.6kW rectifier has extremely high density providing the most power in the least amount of space. A compact 4RU shelf accommodates six rectifiers per 23" shelf and five rectifiers per 19" shelf. Local and remote setup, adjustment, and control is a simple single-step process with the Cordex CXC System Controller. By utilizing TCP/IP technology, complete configuration and monitoring of power equipment is possible through a network web browser. brochure all rectifiers Cordex 3.6kW
Electrical Specifications
Input voltage |
| Nominal |
208 to 277Vac |
| Operating |
176 to 312Vac |
| Extended |
176 to 90Vac (derated power) |
| Input frequency |
45 to 66Hz |
| Power |
3600W continuous/module |
| Power factor |
>0.99 (50 to 100% load) |
| THD |
<5% |
| Efficiency |
>92% |
| Output voltage |
42 to 60Vdc |
| Float Voltage |
48 to 58Vdc |
| Output current |
66A @ 54Vdc (75A max. 48V) |
| Load regulation |
<±0.5% (static) |
| Line regulation |
<±0.1% (static) |
| Transient response |
±2% for 50 to 100% load step, 2ms recovery time |
Noise
| Voice band |
<32dBrnC |
| Wide band |
<30mV RMS (10kHz to 10MHz) |
|
<150mV pk to pk (10kHz to 100MHz) |
| Psophometric |
<1mV |
| Acoustic |
<60dBa @ 1m (3ft) |
Mechanical Specifications
| Dimensions (in/mm) |
6.3 x 3.4 x 11.8 / 160 x 87 x 300 |
| Weight (lb/kg) |
10 / 4.6 |
Features
| Indicators |
AC mains OK — green LED |
|
Module OK — green LED |
|
Module fail — red LED |
| Controls |
CAN interface to CXC Controller |
| Adjustments (via CXC Controller) |
Float voltage, Equalize voltage, High/Low voltage alarm, High voltage shutdown, Current limit, Slope, Start delay |
| Protection |
Current limit/short circuit, Start delay, Input/output fuses, Output high voltage shutdown, Power limiting, Thermal foldback/shutdown, Input transient, AC low line foldback/shutdown |
Environmental Specifications
| Operating Temperature |
-40 to 65°C / -40 to 149°F |
| Storage Temperature |
-40 to 85°C / -40 to 185°F |
| Humidity |
0 to 95% non-condensing |
| Elevation |
-500 to 4000m / -1640 to 13120ft |
| Heat dissipation |
<1176BTU per hour |
Standards
| Safety |
CSA C22.2 No 60950-1-03 |
|
UL 60950-1 1st Edition |
|
CE marked |
|
IEC/EN 60950-1 |
| EMC |
ETSI 300 386 |
| Emissions |
CFR47 (FCC) Part 15 Class B |
|
ICES-03 Class B |
|
EN55022 (CISPR 22) Class B |
|
C-tick (Australia) |
|
EN 61000-3-2 |
|
EN 61000-3-3 |
| Immunity |
EN 61000-4-2 |
|
EN 61000-4-3 |
|
EN 61000-4-4 |
|
EN 61000-4-5 |
|
EN 61000-4-6 |
|
EN 61000-4-11 |
|
ANSI/IEEE C62.41 Cat B3 |
| NEBS |
GR-1089 CORE |
|
GR-69 CORE |
|